Data Sheet for Product

Sample Wiring Diagram for VAV with Reheat (HW or Elec)
Application Configuration
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
H
N
E
1
2
BST
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
SRV
SASC0140R2
NETWORK
CONNECTION
IN 1
OUT A1
OUT A2
OUT A3
OUT D1
OUT D2
OUT D3
OUT D4
OUT D5
OUT D6
OUT D7
OUT D8
IN 2
IN 3
IN 4
IN 5
IN 6
24 VAC LINE
24 VAC NEUTRAL
EARTH
DAMPER
MOTOR
REHEAT
VALVE
-or-
REHEAT
STAGES
QVM
SENSOR
RTS
H
N
E
SASC0144R1
Note: Route wiring from either the bottom opening when using a J-box or from the base sides as shown
in the picture when flat or din rail mounting. The image above is for illustrative purposes only
SASC0145R1
Predator Cover
With Controller
Board (Back View)
RJ-11 Connector
Room Sensor Port
Predator Room
Temperature Sensor
Wiring Recommendations:
IN and AO: 20 to 22 AWG
DO: 18 to 22
AWG
Power: 16 to 18
AWG
LON Network: 22
AWG Level 4
Transformer
Requirements:
Type: Class 2, 24 VAC, 50/60Hz
Predator Wiring Diagrams (Full Point Board Shown).
Page 6 of 11 Document No. 588-894