Data Sheet for Product

Document No. 588-894 Page 5 of 11
Perimeter Heat
This application also supports the optional control of perimeter heat. The algorithm
supports analog, 3-point floating, pulse width modulation, and on/off control of the
perimeter heat. Perimeter heat operates independently of terminal airflow or the
current state of the terminal fan.
Flow Sensor Range
This application has been designed to use the Siemens QVM variable range flow sensor,
(P/N: QVM62.1). The flow sensor has a range of 5, 10, 15 m/s and is jumper adjusted. The
controller should be configured with the same range. The default setting for the sensor and
controller is 10 m/s.
Hardware Map – VAV/CV
Sample Hardware Map for the VAV with Reheat (HW or Elec) Application Configuration
Configuration
Property
Element Input/Output
Type
Factory Hardware Setting
(VAV/CV)
Desired Setting
Settings that need to be
changed from the factory
defaults are shown in
BOLD face type.
statTempOffset - 0°F
0°C
0°F
0°C
inStat
statSetptOffset - 0°F
0°C
0°F
0°C
statTemp TEMP SPACE_TEMP SPACE_TEMP
statSetpt TEMP SPACE_SETPT_TEMP SPACE_SETPT_TEMP
statOvrd DI STAT_SWITCH_DI STAT_SWITCH_DI
IN1 DI, TEMP SPARE2_IN
IN_UNUSED
IN2 DI, TEMP SOURCE_TEMP
IN_UNUSED
IN3 DI, PCT, TEMP OCC_SENSOR_DI
IN_UNUSED
IN4 DI, PCT, TEMP SPARE3_IN
IN_UNUSED
IN5 DI, PCT, TEMP SPARE1_IN
IN_UNUSED
Inputs
IN6 DI, PCT, TEMP VELOCITY_EXT1_PCT VELOCITY_EXT1_PCT
OUTA1 AO FLOW_DMPR_AO
OUT_UNUSED
OUTA2 AO TRM_H_COIL_AO
OUT_UNUSED
OUTA3 AO SPARE2_OUT
OUT_UNUSED
OUTD1 DO, FLT_MTR FLOW_DMPR_FLT_MTR FLOW_DMPR_FLT_MTR
OUTD2 DO, FLT_MTR FLOW_DMPR_FLT_MTR FLOW_DMPR_FLT_MTR
OUTD3 DO, FLT_MTR TRM_H_COIL_FLT_MTR TRM_H_COIL_FLT_MTR
OUTD4 DO, FLT_MTR TRM_H_COIL_FLT_MTR TRM_H_COIL_FLT_MTR
OUTD5 DO, FLT_MTR TRM_FAN_DO
OUT_UNUSED
OUTD6 DO, FLT_MTR PERIM_H_COIL_FLT_MTR
OUT_UNUSED
OUTD7 DO, FLT_MTR PERIM_H_COIL_FLT_MTR
OUT_UNUSED
outputs
OUTD8 DO, FLT_MTR SPARE1_OUT
OUT_UNUSED