Installation Instructions
Table Of Contents
Installation Instructions
Document No. 540-148
August 15, 2012
Table 1. BACnet TEC or ATEC Controller
Wiring Diagram.
Pin Wire
1 Not Used
6 TX/RX
3 Room Temp/
Setpoint,
Override
4 Common
5 TX/RX
2 GND
Twisted Pair
SASC0126R1
1
6
1
6
Pair 1
3
4
3
4
Pair 2
5
2
5
2
Pair 3
9. Plug the terminated cable into the RJ-11 port on the
back of the printed circuit board (PCB).
10. Feed the extra cable back through the hole in the
rubber insulator.
11. Snap the sensor front to the sensor base plate:
a. Hook the sensor front to the bottom latches.
b. Push the top of the sensor front into place until it
latches.
12. Tighten the sensor retaining screw with an Allen
wrench. See
Figure 3.
13. Connect the sensor to the RTS port on the controller.
The installation is now complete.
Electrical Box and Rough-in Mounting,
Typical
1. If a locator is attached to the rough-in device, remove
the locator by removing the two screws and lightly
rocking the locator to pull it free.
2. Untie the twist tie and pull about three inches (75 mm)
of the sensor cable into the space.
3. If you have a single-sensor electrical box, install the
electrical box adapter plate. See
Figure 5.
If you have a double-sensor electrical box, install the
required mounting plate(s).
If you use a universal adapter kit for a retrofit job,
install the multi-slotted plate in place of the electrical
box adapter plate. See
Figure 5.
Figure 5. Electrical Box and Rough-in
Mounting (Typical).
4. Pull the cable from the wall, through the required
mounting hardware in the order shown.
5. Install the two sensor mounting screws provided but do
not tighten.
6. Mount the sensor base plate on the wall, noting the UP
arrow on the stabilizer plate:
a. Level the sensor base plate for appearance only.
b. Tighten the two mounting screws to the sensor
base plate.
CAUTION:
Over-tightening may cause the sensor base
plate to crack or bend.
7. Continue with Drywall Mounting (No Rough-in,
Typical), Steps 7 through 13.
The installation is now complete.
Accessories
Table 2. Room Sensor Pre-terminated Cables.
Controller
Product
Number
Plenum
Description
540-135 or
588-100A
25-foot (7.6 m) cable
with connections
540-136 or
588-100B
50-foot (15.2 m) cable
with connections
540-137 or
588-100C
100-foot (30.5 m) cable
with connections