TALON® Analog Room Temperature Sensor,
10K Ω Thermistor
Page 1 of 4
Product Description
These sensors work with Siemens controllers. The
sensors use a 10K ohm thermistor to detect temperature.
The effective sensing range is 55°F to 95°F (13°C to
35°C).
NOTE: Any of these sensors can be mounted on
electrical boxes, stud-type mounting brackets, or
drywall. Obtain the necessary mounting hardware
and follow the appropriate mounting procedures
for the type of installation required.
Product Numbers
Product Numbers
TALON
Logo**
No Logo
Description
587-614B 540-661B Sensing only
587-618B 540-671B Override and setpoint
587-620CB -- Override, setpoint and
temperature display,
Celsius
587-620FB -- Override, setpoint and
temperature display,
Fahrenheit
Expected Installation Time
20 minutes
Caution Notation
CAUTION:
Equipment damage or loss of
data may occur if you do not
follow the procedures as
specified.
Item Number 540-148, Rev. CA
Required Tools
Phillips size 1 or 2 screwdriver
1/16-inch Allen wrench, (Part Number 192-632,
package of 5)
Small and medium flat-blade screwdrivers
Medium-duty electric drill
3/16-inch drill bit
1-inch hole saw
Hammer
Utility knife
Wire cutters
Small level
Tape measure
Marker or pencil
If using non-preterminated cables (or if cables are
damaged), you also need:
Room sensor connector tool (RJ-11 crimping tool)
Room sensor connector kit
Prerequisites
Appropriate field wiring (standard six-conductor
room sensor cables, plenum) within the maximum
wiring run length for the individual field panel or
equipment controller must be installed. The
maximum recommended length is 100-feet
(30.5 m).
See Table 2 for cable product numbers.
All wiring must comply with National Electric Code
(NEC) and local regulations.
Figure 1. Room Temperature Sensor
(Shows All Options).