User Guide
Installation Instructions
Document No. 538-495
March 17, 2005
Outside Air Sensor,
4 to 20 mA
Product Description
The Outside Air Sensor provides a 4 to 20 mA input
for temperature control to a controller.
Product Number
536-768 –58°F to 122°F (–50°C to 50°C) range
Required Tools
• Power screwdriver with standard screw
chuck or medium flat-blade screwdriver
• Wire cutter/stripper
• Drill and drill bits
Expected Installation Time
Two hours
Prerequisites
• The appropriate field wiring, within the
maximum wiring run length for the individual
field panel or equipment controller, should
be pulled through the conduit to a utility box
near the sensor location.
• Verify the distance between the utility
mounting box and the outlet end of the
pulling elbow. If the distance is less than
22 inches (56 cm), follow Option A. If the
distance is greater than 22 inches (56 cm),
and less than six feet (1.8 m), follow
Option B.
NOTE: The distance between the utility
mounting box and the pulling elbow
cannot exceed six feet (1.8 m).
• The preferred sensor location is the north
side of the building, in the shade, where the
sensor is protected from direct or indirect
sunlight and drafts from exhaust vents, etc.
Instructions
NOTE: All wiring must comply with National
Electrical Code (NEC) and local regulations.
Option A Installation
NOTE: If replacing an existing sensor, disconnect
the positive (+) 26V supply lead of the field
wiring from the controller termination board
or block.
1. Use an existing opening or drill an opening
through the outside wall for 1/2-inch (13 mm)
rigid conduit. The sensor must be located three
to six inches (7.5 to 15 cm) from the wall
2. Feed the sensor leads through the rigid conduit
to the utility box located on the inside of the
building. Thread the pulling elbow/sensor
assembly onto the conduit as shown in Figure 1.
3. Rotate the sensor so that the shield points down
and shades the sensing element from direct and
indirect sunlight.
Figure 1. Outside Air Sensor, Option A Installation.
Item Number: 538-495-05, Rev. 011 Page 1 of 3



