Datasheet
Single-Phase Transformers
Safety, Isolating, Control and Mains Transformers
General data
11/11
Siemens IC 10 · 2011
11
Secondary-side short-circuit and overload protection with motor starter protector
1)
Two-pole or single-pole motor starter protectors can be connected
(3 conducting paths in series), see circuit diagram on page 11/7.
Transformer Rated power
P
n
Motor starter protectors
Version:
Motor protection
1)
Rated output voltage
U
2N
in V
Type kVA Type 230 115 110 42 24
4AM transformers
4AM23 4 0.025 3RV20 11-@@@10 0AA 0DA 0DA 0HA 1AA
Set value in A 0.14 0.26 0.29 0.75 1.3
4AM26 4 0.04 3RV20 11-@@@10 0CA 0FA 0FA 0KA 1CA
Set value in A 0.21 0.41 0.45 1.2 2.1
4AM32 4 0.063 3RV20 11-@@@10 0EA 0HA 0HA 1BA 1EA
Set value in A 0.34 0.68 0.72 1.9 3.3
4AM34 4 0.1 3RV20 11-@@@10 0GA 0KA 0KA 1DA 1GA
Set value in A 0.55 1.1 1.14 3 5.2
4AM38 4 0.16 3RV20 11-@@@10 0JA 1BA 1BA 1FA 1JA
Set value in A 0.86 1.72 1.82 4.8 8.4
4AM40 4 0.25 3RV20 11-@@@10 1AA 1DA 1DA 1HA --
3RV20 21-@@@10 -- -- -- -- 4AA
Set value in A 1.37 2.7 2.8 7.4 13
4AM43 4 0.315 3RV20 11-@@@10 1BA 1EA 1EA 1JA --
3RV20 21-@@@10 -- -- -- -- 4BA
Set value in A 1.72 3.4 3.6 9.4 16.5
4AM46 4 0.4 3RV20 11-@@@10 1CA 1FA 1FA 1KA --
3RV20 21-@@@10 -- -- -- -- 4CA
Set value in A 2.2 4.4 4.6 12 21
4AM48 4 0.5 3RV20 11-@@@10 1DA 1GA 1GA -- --
3RV20 21-@@@10 -- -- -- 4AA --
3RV10 31-@@@10 -- -- -- -- 4EA
Set value in A 2.7 5.4 5.7 15 26
4AM52 4 0.63 3RV20 11-@@@10 1EA 1HA 1HA -- --
3RV20 21-@@@10 -- -- -- 4BA --
3RV10 31-@@@10 -- -- -- -- 4FA
Set value in A 3.4 6.8 7.2 18.8 33
4AM55 4 0.8 3RV20 11-@@@10 1FA 1JA 1JA -- --
3RV20 21-@@@10 -- -- -- 4DA --
3RV10 31-@@@10 -- -- -- -- 4GA
Set value in A 4.4 8.8 9.2 24 42
4AM57 4 1 3RV20 11-@@@10 1GA 1KA 1KA -- --
3RV10 31-@@@10 -- -- -- 4EA --
3RV10 41-@@@10 -- -- -- -- 4JA
Set value in A 5.4 10.8 11.4 30 52
4AM61 4 1.6 3RV20 11-@@@10 1JA -- -- -- --
3RV10 31-@@@10 -- 4BA 4BA 4HA --
3RV10 41-@@@10 -- -- -- -- 4LA
Set value in A 8.6 17 18.5 48 81
4AM64 4 2 3RV20 11-@@@10 1KA -- -- -- --
3RV10 31-@@@10 -- 4DA 4DA -- --
3RV10 41-@@@10 -- -- -- 4JA 4MA
Set value in A 10.9 22 23 60 101
4AM65 4 2.5 3RV20 21-@@@10 4AA -- -- -- --
3RV10 31-@@@10 -- 4EA 4EA -- --
3RV10 41-@@@10 -- -- -- 4KA --
3VF32 11-@@@@@-0AA0 -- -- -- -- 1BU41
Set value in A 13.6 27 28 72 125
4AT transformers
4AT30 3 4 3RV20 21-@@@10 4CA -- -- -- --
3RV10 31-@@@10 -- 4GA -- -- --
Set value in A 21 41 -- -- --
4AT36 1 5 3RV10 31-@@@10 4EA -- -- -- --
3RV10 41-@@@10 -- 4JA -- -- --
Set value in A 26 51 -- -- --
4AT36 3 6.3 3RV10 31-@@@10 4FA -- -- -- --
3RV10 41-@@@10 -- 4KA -- -- --
Set value in A 32 64 -- -- --
4AT39 1 8 3RV10 31-@@@10 4GA -- -- -- --
3RV10 41-@@@10 -- 4LA -- -- --
Set value in A 41 81 -- -- --
4AT39 3 10 3RV10 41-@@@10 4JA 4MA -- -- --
Set value in A 51 100 -- -- --