Data Sheet
Product component
● Trip indicator
No
● Auxiliary switch
No
● Voltage trigger
No
● undervoltage release
No
● undervoltage release with leading contact
No
Product extension / optional / motor drive Yes
Product function
Product function
● of thermal overload trip unit
without
● Ground fault protection
No
● for neutral conductors / Short-circuit and
overload proof
No
● Overload protection
No
Short circuit
Operational short-circuit current breaking capacity
(Ics)
● at 240 V / rated value
75kA
● at 415 V / rated value
70kA
● at 500 V / rated value
30kA
● at 690 V / rated value
10kA
Maximum short-circuit current breaking capacity (Icu)
● at 240 V / rated value
100kA
● at 415 V / rated value
70kA
● at 440 V / rated value
50kA
● at 480 V / acc. to NEMA / rated value
50kA
● at 500 V / rated value
40kA
● at 600 V / acc. to NEMA / rated value
30kA
● at 690 V / rated value
20kA
Connections
Arrangement of electrical connectors / for main
current circuit
front side
Type of electrical connection / for main current circuit screw-type terminals
Mechanical Design
Height 279.5mm
Width 190mm
Depth 138.5mm
Mounting type fixed mounting
● during operation
-25...+70°C
● during storage
-40...+80°C
3VL5763-2AA36-0AA0 Subject to change without notice
Page 3/
5
09/13/2019 © Copyright Siemens