Data Sheet
Electrical endurance (switching cycles) / at AC-1 / at
380/415 V 50/60 Hz
9000
Electrical endurance (switching cycles) / at AC-1 / at
690 V 50/60 Hz
5000
Electrical endurance (switching cycles) / at 480 V / at
50/60 Hz
9000
Electrical endurance (switching cycles) / at 600 V / at
50/60 Hz
9000
Neutral conductors / upgradeable/retrofittable No
Ground fault monitoring version Without
Product function
● communication function
No
● Phase failure detection
No
● other measurement function
No
Current
Marking / acc. to UL 489 / 100%-rated breaker No
Max. rated operational current of the frame size 150A
Rated continuous current Iu 80A
Operating current
● at 40 °C
80A
● at 45 °C
80A
● at 50 °C
80A
● at 55 °C
80A
● at 60 °C
80A
● at 65 °C
80A
● at 70 °C
80A
Adjustable parameters
Adjustable response value current / li min. 240A
Adjustable response value current / li max. 1200A
Ground fault protection / tripping switchable /
I2t=ON/OFF
No
Mechanical Design
Height [in] 7.8in
Height 198mm
Width [in] 4.1in
Width 105mm
Depth [in] 3.4in
Depth 86mm
Connections
Arrangement of electrical connectors / for main
current circuit
Without connection
Type of electrical connection / for main current circuit Without
3VA6180-1MS31-0AA0 Subject to change without notice
Page 2/
7
07/25/2019 © Copyright Siemens