Data Sheet

Data sheet 3VA5195-6ED11-1AA0
circuit breaker 3VA5 UL frame 125 breaking capacity class H 50kA
@ 277V 1-pole, line protection TM210, FTFM, In=15A overload
protection Ir=15A fixed short-circuit protection Ii=20 x In UL 489 SB
(naval), 50° C without connection
Model
Product brand name SENTRON
Product designation Molded-case circuit breaker
Product designation / according to UL file H5EAM
Product version System protection
Design of the load switch / acc. to UL 489 / Heating,
Air Conditioning, and Refrigeration circuit breaker
(HACR Type)
Yes
Design of the overcurrent release TM210
Protective function of the overcurrent release LI
Number of poles 1
General technical data
Power loss [W] / maximum 3.2W
Active power loss / for rated value of the current / at
AC / in hot operating state / per pole
3.2W
Latching - endurance 15000
Electrical endurance (switching cycles) / at AC-1 / at
380/415 V 50/60 Hz
8000