Data Sheet
Ground fault monitoring version Without
Product function
● communication function
Yes
● other measurement function
Yes
Net weight 5.242kg
Current
Max. rated operational current of the frame size 630A
Rated continuous current Iu 630A
Operating current
● at 40 °C
630A
● at 45 °C
600A
● at 50 °C
570A
● at 55 °C
540A
● at 60 °C
510A
● at 65 °C
480A
● at 70 °C
450A
Switching capacity according to IEC 60947
Switching capacity class of the circuit breaker M
Maximum short-circuit current breaking capacity (Icu)
● at 240 V
85kA
● at 415 V
55kA
● at 440 V
55kA
● at 500 V
36kA
● at 690 V
6kA
Operational short-circuit current breaking capacity
(Ics)
● at 240 V
85kA
● at 415 V
55kA
● at 440 V
55kA
● at 500 V
36kA
● at 690 V
6kA
Short-circuit current making capacity (Icm)
● at 240 V
187kA
● at 415 V
121kA
● at 690 V
9kA
Adjustable parameters
Adjustable response value current / lr min. 252A
Adjustable response value current / Ir max. 630A
Adjustable response value time / tr min. 0.5
Adjustable response value time / tr max. 12
Adjustable response value current / Isd min. 378A