Data Sheet
Ground fault monitoring version Summation current formation L-conductor
Product function
● communication function
No
● other measurement function
No
Net weight 4.3kg
Current
Max. rated operational current of the frame size 630A
Rated continuous current Iu 400A
Operating current
● at 40 °C
400A
● at 45 °C
400A
● at 50 °C
400A
● at 55 °C
384A
● at 60 °C
372A
● at 65 °C
356A
● at 70 °C
340A
Switching capacity according to IEC 60947
Switching capacity class of the circuit breaker M
Maximum short-circuit current breaking capacity (Icu)
● at 240 V
85kA
● at 415 V
55kA
● at 440 V
55kA
● at 500 V
36kA
● at 690 V
6kA
Operational short-circuit current breaking capacity
(Ics)
● at 240 V
85kA
● at 415 V
55kA
● at 440 V
55kA
● at 500 V
36kA
● at 690 V
6kA
Short-circuit current making capacity (Icm)
● at 240 V
187kA
● at 415 V
121kA
● at 690 V
9kA
Adjustable parameters
Adjustable response value current / lr min. 160A
Adjustable response value current / Ir max. 400A
Adjustable response value time / tr min. 0.5
Adjustable response value time / tr max. 17
3VA2440-5HM32-0AA0 Subject to change without notice
Page 2/
7
09/14/2019 © Copyright Siemens