Data Sheet

Data sheet 3VA2325-7KP32-0AA0
circuit breaker 3VA2 IEC frame 400 breaking capacity class C
Icu=110kA @ 415V 3-pole, line protection ETU850, LSI, In=250A
overload protection Ir=100A...250A short-circuit protection
Isd=0.6..10x In, Ii=1.5..12x In N conductor protection optionally with
external current transformer, up to 160% nut keeper kit
Model
Product brand name SENTRON
Product designation Molded case circuit breaker
Product version Line protection
Design of the overcurrent release ETU850
Protective function of the overcurrent release LSI
Number of poles 3
General technical data
Rated insulation voltage Ui 800V
Max. rated operational voltage Ue with AC 50/60Hz 690V
Power loss [W] / maximum 37.5W
Active power loss / for rated value of the current / at
AC / in hot operating state / per pole
12.5W
Latching - endurance 20000
Electrical endurance (switching cycles) / at AC-1 / at
380/415 V 50/60 Hz
6000
Electrical endurance (switching cycles) / at AC-1 / at
690 V 50/60 Hz
5000
Neutral conductors / upgradeable/retrofittable Yes
3VA2325-7KP32-0AA0 Subject to change without notice
Page 1/
7
09/14/2019 © Copyright Siemens

Summary of content (7 pages)