Data Sheet
Adjustable parameters
Adjustable response value current / lr min. 100A
Adjustable response value current / Ir max. 250A
Adjustable response value time / tr min. 3
Adjustable response value time / tr max. 30
Adjustable response value current / Isd min. 300A
Adjustable response value current / Isd max. 3750A
Short-term delayed / tripping switchable /
I2t=ON/OFF
No
Adjustable response value time / tsd min. 0.03s
Adjustable response value time / tsd max. 0.03s
Adjustable response value time / tsd min. 0s
Adjustable response value time / tsd max. 0s
Adjustable response value current / li min. 750A
Adjustable response value current / li max. 3750A
Ground fault protection can be switched ON/OFF Yes
Ground fault protection / tripping switchable /
I2t=ON/OFF
Yes
Adjustable response value current / lg min. 50A
Adjustable response value current / lg max. 250A
Adjustable response value current / tg min. 0.05s
Adjustable response value current / tg max. 0.8s
Adjustable response value current / for G-tripping /
with I2t characteristic / min.
0.2A
Adjustable response value current / for G-tripping /
with I2t characteristic / max.
1A
Mechanical Design
Height [in] 9.8in
Height 248mm
Width [in] 5.4in
Width 138mm
Depth [in] 4.3in
Depth 110mm
Connections
Arrangement of electrical connectors / for main
current circuit
Front terminal
Type of electrical connection / for main current circuit Lug terminal
Type of connectable conductor cross-section,
connection screw, width x thickness , min.
20 x 1
Type of connectable conductor cross-section,
connection screw, width x thickness , max.
35 x 10
Auxiliary circuit
Number of CO contacts / for auxiliary contacts 0
3VA2325-5MQ32-0AA0 Subject to change without notice
Page 3/
7
09/13/2019 © Copyright Siemens