Data Sheet

Ground fault monitoring version Without
Product function
● communication function
No
● other measurement function
No
Net weight 2.93kg
Current
Max. rated operational current of the frame size 160A
Rated continuous current Iu 40A
Operating current
● at 40 °C
40A
● at 45 °C
40A
● at 50 °C
40A
● at 55 °C
40A
● at 60 °C
40A
● at 65 °C
40A
● at 70 °C
40A
Switching capacity according to IEC 60947
Switching capacity class of the circuit breaker L
Maximum short-circuit current breaking capacity (Icu)
● at 240 V
200kA
● at 415 V
150kA
● at 440 V
150kA
● at 500 V
100kA
● at 690 V
24kA
Operational short-circuit current breaking capacity
(Ics)
● at 240 V
200kA
● at 415 V
150kA
● at 440 V
150kA
● at 500 V
100kA
● at 690 V
18kA
Short-circuit current making capacity (Icm)
● at 240 V
440kA
● at 415 V
330kA
● at 440 V
330kA
● at 500 V
220kA
● at 690 V
50kA
Adjustable parameters
Adjustable response value current / lr min. 16A
Adjustable response value current / Ir max. 40A
Adjustable response value time / tr min. 0.5
3VA2140-8HL42-0AA0 Subject to change without notice
Page 2/
7
09/14/2019 © Copyright Siemens