Datasheet
Neutral conductors / upgradeable/retrofittable No
Ground fault monitoring version Without
Product function
● communication function
No
● other measurement function
No
Net weight 0.6kg
Electricity
Max. rated operational voltage of the size of the
circuit-breaker
160A
Rated continuous current Iu 32A
Operating current
● at 40 °C
32A
● at 45 °C
32A
● at 50 °C
32A
● at 55 °C
31.04A
● at 60 °C
31A
● at 65 °C
30A
● at 70 °C
30A
Switching capacity according to IEC 60947
Switching capacity class of the circuit breaker S
Maximum short-circuit current breaking capacity (Icu)
● at 240 V
55kA
● at 415 V
36kA
Operational short-circuit current breaking capacity
(Ics)
● at 240 V
55kA
● at 415 V
36kA
Short-circuit current making capacity (Icm)
● at 240 V
121kA
● at 415 V
76kA
Adjustable parameters
Adjustable response value current / lr min. 32A
Adjustable response value current / Ir max. 32A
Short-term delayed / tripping switchable /
I2t=ON/OFF
No
Adjustable response value current / li min. 320A
Adjustable response value current / li max. 320A
Ground fault protection / tripping switchable /
I2t=ON/OFF
No
Mechanical Design
Height [in] 5.1in
3VA1132-4ED26-0AA0 Subject to change without notice
Page 2/
7