User Manual
3UG4.1 line monitoring relay
6.2 3UG4511 line monitoring relay
3UG4 / 3RR2 monitoring relays
94 Manual, 02/2013, NEB927043002000/RS-AA/002
3UG45 11-..N 3UG45 11-..P 3UG45 11-..Q
Type of voltage of the controlled
supply voltage
AC
Control supply voltage
• at 50 Hz at AC rated value
V
160 … 260 320 … 500 420 … 690
• at 60 Hz at AC rated value
V
160 … 260 320 … 500 420 … 690
Working range factor supply voltage
rated value
• at 50 Hz for AC
1
• at 60 Hz for AC
1
Impulse voltage resistance rated
value
kV
6
Recorded real power W 2
Protection class IP IP20
Electromagnetic compatibility IEC 60947-1 /
IEC 61000-6-2 /
IEC 61000-6-4
Operating current at 17 V minimum mA 5
Continuous current of the DIAZED
fuse link of the output relay
A 4
Resistance against vibration
according to IEC 60068-2-6
1 … 6 Hz: 15 mm,
6 … 500 Hz: 2g
Resistance against shock according
to IEC 60068-2-27
sinusoidal half-wave
15g / 11 ms
Current carrying capacity of output
relay
• at AC-15
– at 250 V at 50/60 Hz
A
3
– at 400 V at 50/60 Hz
A
3
• at DC-13
– at 24 V
A
1
– at 125 V
A
0.2
– at 250 V
A
0.1
Installation altitude at a height over
sea level maximum
m
2 000
Conductor-bound parasitic coupling
BURST according to IEC 61000-4-4
2 kV
Conductor-bound parasitic coupling
conductor-earth SURGE according
to IEC 61000-4-5
2 kV
Conductor-bound parasitic coupling
conductor-conductor SURGE
according to IEC 61000-4-5
1 kV