User Manual

3UG4501 filling level monitoring relay
5.7 Technical data
3UG4 / 3RR2 monitoring relays
84 Manual, 02/2013, NEB927043002000/RS-AA/002
3UG4501-..A.. 3UG4501-..W..
Continuous current of the DIAZED fuse link of
the output relay
A 4
Resistance against vibration according to IEC
60068-2-6
1 ... 6 Hz: 15 mm, 6 ... 500 Hz: 2g
Resistance against shock according to IEC
60068-2-27
sinusoidal half-wave 15g / 11 ms
Installation altitude at a height over sea level
maximum
m 2 000
Current carrying capacity of output relay
at AC-15
at 250 V at 50/60 Hz
A 3
at 400 V at 50/60 Hz
A
3
at DC-13
at 24 V
A 1
at 125 V
A
0.2
at 250 V
A
0.1
Conductor-bound parasitic coupling BURST
according to IEC 61000-4-4
2 kV
Conductor-bound parasitic coupling conductor-
earth SURGE according to IEC 61000-4-5
2 kV
Conductor-bound parasitic coupling conductor-
conductor SURGE according to IEC 61000-4-5
1 kV
Electrostatic discharge according to IEC 61000-4-
2
6 kV contact discharge / 8 kV air discharge
Field-bound parasitic coupling according to IEC
61000-4-3
10 V/m
Insulation voltage for overvoltage category III
according to IEC 60664 with degree of pollution
3 rated value
V 300
Degree of pollution 3
Apparent power consumed
at 24 V for AC maximum
V·A
2
at 240 V for AC maximum
V·A 4
Ambient temperature
during operating
°C
-25 … +60
during storage
°C -40 … +80
during transport
°C -40 … +80
Galvanic isolation between entrance and outlet
Yes
Galvanic isolation between the outputs No