User Manual

3UG4501 filling level monitoring relay
5.7 Technical data
3UG4 / 3RR2 monitoring relays
Manual, 02/2013, NEB927043002000/RS-AA/002
83
5.7 Technical data
General technical details
3UG4501-..A.. 3UG4501-..W..
Product function Monitoring relay for level monitoring
Response time maximum s 0.3
Relative metering precision % 20
Temperature drift per °C %/°C 1
Relative repeat accuracy % 1
Manufacturer article number of the optional
sensor
2-pole and 3-pole sensors 3UG3207
Cable length of the sensor maximum m 100
Type of display LED Yes
Product function
response sensitivity adjustable
Yes
outlet monitoring adjustable
Yes
inlet monitoring adjustable
Yes
reset external
Yes
Starting time after the control supply voltage has
been applied
ms
500
Type of voltage of the controlled supply voltage AC/DC
Control supply voltage
at 50 Hz at AC
rated value
V 24 24 … 240
at 60 Hz at AC
rated value
V 24 24 … 240
for DC
rated value
V 24 24 … 240
Working range factor supply voltage rated value
at 50 Hz
for AC
0.85 … 1.1
at 60 Hz
for AC
0.85 … 1.1
for DC
0.85 … 1.1
Impulse voltage resistance rated value kV
4
Recorded real power W 2
Protection class IP IP20
Electromagnetic compatibility IEC 60947-1 / IEC 61000-6-2 / IEC 61000-6-4
Operating current at 17 V minimum mA 5