3UG4501 filling level monitoring relay   
5.4 Operation 
  3UG4 / 3RR2 monitoring relays 
80  Manual, 02/2013, NEB927043002000/RS-AA/002 
5.4  Operation 
Parameters 
The following parameters can be set on the relevant rotary button using a screwdriver: 
Table 5- 2  Parameter information, 3UG4501 filling level monitoring relay 
Setting range 
Parameters  Operating 
elements 
2)
Minimum value  Maximum value 
Increment 
Monitoring mode
1)
: 
drainage control (OV) or inflow 
control (UN) 
3  --  --  -- 
Sensor sensitivity (R sens)  4  2 kΩ  200 kΩ  Continuous 
Tripping delay time (Delay)  5  0.5 s  10 s  Continuous 
1)
 By operating the rotary button, it is possible to choose between drainage control (OV) and 
inflow control (UN) depending on the application (one-point control or two-point control). 
2)
 The position digits refer to the front view in Chapter "Operator controls and connection 
terminals (Page 76)." 
Chapter "Circuit diagrams (Page 81)" shows the wiring examples for the different monitoring 
modes. 
The paramete
rs are defined in Chapter "Paramete
rs (Page 351)." 
Required tools 
The same screwdriver can be used to set the parameters as for mounting the filling level 
monitoring relays. 
5.5  Diagnostics 
5.5.1  Diagnostics with LED 
Depending on the liquid level, the output relay switches in accordance with its set relay 
switching behavior (drainage control OV, inflow control UN). If the output relay responds 
(contact 11-12 open, contact 11-14 closed), the yellow LED next to the contact symbol on 
the device cover lights up. 
The switching behavior of the output relay is shown in Chapter "Functions (Page 77)." 