  3RR2 current monitoring relays 
  4.5 3RR22 current monitoring relays 
3UG4 / 3RR2 monitoring relays 
Manual, 02/2013, NEB927043002000/RS-AA/002 
65 
4.5.4  Diagnostics 
Display information 
The display is divided into three different areas. 
23
1
①  Current measured value or fault symbol 
②  Type of monitoring 
③  Symbols for the semiconductor contact (left) and the CO contact (right) 
Meaning of the information on the display 
Note 
Indications in the event of a fault 
The symbols on the display flash to indicate an error. 
The following statuses and faults are indicated on the display as a diagnostics message with 
flashing symbols: 
Display 
area 
Symbol  Meaning 
① 
12.5A  Displays the measured current 
① 
n x I▲  Flashing: Current is above the set blocking current 
① 
I>>
Flashing: Fault current detected 
① 
L
  Flashing: Cable break/phase failure detected 
① 
Flashing: Incorrect phase sequence detected 
② 
Monitoring for current overshoot 
② 
Monitoring for current undershoot 
② 
Range monitoring (monitoring for current overshoot and current undershoot) 
② 
Current is in correct range 
② 
A current overshoot has occurred 
② 
A current undershoot has occurred 