User Manual
3RR2 current monitoring relays   
4.4 3RR21 current monitoring relays 
  3UG4 / 3RR2 monitoring relays 
54  Manual, 02/2013, NEB927043002000/RS-AA/002 
Connections 3RR2142 (size S0) 
  3RR2142-1....  3RR2142-2.... 
Design  of  the  electrical  connection     
•  for  main  current  circuit 
screw-type  terminals  spring-loaded  terminals 
•  for  auxiliary  and  control  current  circuit 
screw-type  terminals  spring-loaded  terminals 
Product  function     
•  removable  terminal  for  main  circuit 
No   
•  removable  terminal  for  auxiliary  and  control 
circuit 
  Yes   
Type  of  the  connectable  conductor  cross-section  
•  for  main  contacts 
–  solid 
  2x  (1  ...  2.5  mm
2
),   
2x  (2.5  ...  10  mm
2
) 
1x  (1  ...  10  mm
2
) 
–  stranded 
  —   
–  finely  stranded 
–  with  conductor  end  processing 
2x  (1  ...  2.5  mm
2
),   
2x  (2.5  ...  6  mm
2
),   
1x  10  mm
2
1x  (1  ...  6  mm
2
) 
–  without  conductor  final  cutting 
  —  1x  (1  ...  6  mm
2
) 
•  for  AWG  conductors  for  main  contacts 
2  x  (16  ...  14),   
2x  (14  ...  8) 
1x  (18  ...  8) 
•  for  auxiliary  contacts 
–  solid 
  1x  (0.5  ...  4  mm
2
),   
2x  (0.5  ...  2.5  mm
2
) 
–  finely  stranded 
–  with  conductor  end  processing 
1x  (0.5  ...  2.5  mm
2
),   
2x  (0.5  ...  1.5  mm
2
) 
2x  (0.25  ...  1.5  mm
2
) 
–  without  conductor  final  cutting 
  —  2x  (0.25  ...  1.5  mm
2
) 
•  for  AWG  conductors  for  auxiliary  contacts 
2x  (20  ...  14)  2x  (24  ...  16) 
Tightening  torque     
•  with  screw-type  terminals 
N·m 
0.8 … 1.2   
Verification  of  suitability  
CE / UL / CSA   