User Manual

3RR2 current monitoring relays
4.4 3RR21 current monitoring relays
3UG4 / 3RR2 monitoring relays
Manual, 02/2013, NEB927043002000/RS-AA/002
53
Connections 3RR2141 (size S00)
3RR2141-1.... 3RR2141-2....
Design of the electrical connection
for main current circuit
screw-type terminals spring-loaded terminals
for auxiliary and control current circuit
screw-type terminals spring-loaded terminals
Product function
removable terminal for main circuit
No
removable terminal for auxiliary and control
circuit
Yes
Type of the connectable conductor cross-section
for main contacts
solid
2x (0.5 ... 1.5 mm
2
),
2x (0.75 ... 2.5 mm
2
),
2x (1 ... 4 mm
2
)
1x (0.5 ... 4 mm
2
)
stranded
finely stranded
with conductor end processing
2x (0.5 ... 1.5 mm
2
),
2x (0.75 ... 2.5 mm
2
)
1x (0.5 ... 2.5 mm
2
)
without conductor final cutting
1x (0.5 ... 2.5 mm
2
)
for AWG conductors for main contacts
1x 12, 2x (20 ... 14) 1x (20 ... 12)
for auxiliary contacts
solid
1x (0.5 ... 4 mm
2
),
2x (0.5 ... 2.5 mm
2
)
finely stranded
with conductor end processing
1x (0.5 ... 2.5 mm
2
),
2x (0.5 ... 1.5 mm
2
)
2x (0.25 ... 1.5 mm
2
)
without conductor final cutting
2x (0.25 ... 1.5 mm
2
)
for AWG conductors for auxiliary contacts
2x (20 ... 14) 2x (24 ... 16)
Tightening torque
with screw-type terminals
N·m
0.8 … 1.2
Verification of suitability
CE / UL / CSA