User Manual

3RR2 current monitoring relays
4.3 Performance features of current monitoring relays
3UG4 / 3RR2 monitoring relays
Manual, 02/2013, NEB927043002000/RS-AA/002
43
4.3 Performance features of current monitoring relays
Table 4- 2 Performance features of 3RR2 current monitoring relays
Current monitoring relays with analog setting Current monitoring relays with digital setting
Functions/Parameters
3RR2141-.A.30 3RR2142-.A.30 3RR2241-.F.30 3RR2242-.F.30
Rated current 1.6 to 16 A 4 to 40 A 1.6 to 16 A 4 to 40 A
Frequency range AC 50/60 Hz AC 50/60 Hz AC 20 to 400 Hz AC 20 to 400 Hz
Supply voltage U
s
-.AA30: 24 V AC/DC
-.AW30: 24 to 240 V AC/DC
-.FA30: 24 V AC/DC
-.FW30: 24 to 240 V AC/DC
Monitoring for current
overshoots and/or
undershoots
2-phase 2-phase 3-phase 3-phase
Contacts 1 CO contact 1 CO contact 1 CO contact / 1
semiconductor output
1 CO contact / 1
semiconductor output
4.3.1 General data
Table 4- 3 General data for 3RR2 current monitoring relays
Feature Benefit 3RR21 Basic,
analog setting
3RR22 Standard,
digital setting
Sizes
The devices are matched to the dimensions, connections
and technical features of the other devices in the SIRIUS
modular system.
The devices permit the mounting of slim-line and compact
load feeders in widths of 45 mm (S00 and S0).
The devices make configuration easier.
S00, S0 S00, S0
Current range
The devices are matched to the other devices in the
SIRIUS modular system
Just 1 option per size with a wide setting range makes
configuration easy.
S00: 1.6 to 16 A
S0: 4.0 to 40 A
S00: 1.6 to 16 A