  14.2 Accessories for 3UG4 monitoring relays 
3UG4 / 3RR2 monitoring relays 
Manual, 02/2013, NEB927043002000/RS-AA/002 
321 
Technical data 
Table 14- 10  Technical data - 3UL22 summation current transformer 
Order number    3UL2201  3UL2202  3UL2203 
Rated insulating voltage Ui  (50/60 Hz) V 
AC 
690  1000 
Rated residual current IΔn 
without a response delay 
A  0,3 ... 1  0,3 ... 40  0,3 ... 40 
Permissible ambient 
temperature 
°C  -20 ... +70 
Feed-through opening  mm  40  65  120 
For Protodur cable 
push-through 
max. mm
2
  4 x 95  4 x 240  8 x 300 
14.2.5  3UL23 residual current transformers for 3UG4625 monitoring relays 
Description 
3UL23 residual current transformers detect fault currents in machines and systems. 
Together with the residual current monitoring relay or the 3UF7510 SIMOCODE motor 
management and control device ground-fault module, residual current monitoring and 
ground-fault monitoring are possible. The 3UL23 residual current transformer is available in 
six sizes with bushing opening diameters of ∅ 35 mm, ∅ 55 mm, ∅ 80 mm, ∅ 110 mm, 
∅ 140 mm, and ∅ 210 mm. 
14.2.5.1  General information 
Various circuit types with resulting fault currents 
The following table shows various circuit types and the resulting fault currents in the event of 
a ground fault. Circuits 1 to 6 create pure AC fault currents or AC fault currents with a 
pulsating direct fault current component. This type of fault current can be detected by type
 A transformers in accordance with DIN VDE 0100-530, such as 3UL23 residual current 
transformers. 
Note 
3UG4.25 residual current monitoring relays are only suitable for use with 3UL23 residual 
current transformers. 