User Manual

3UG463. voltage monitoring relay
11.7 Technical data
3UG4 / 3RR2 monitoring relays
276 Manual, 02/2013, NEB927043002000/RS-AA/002
3UG463.-1.A 3UG463.-1.L 3UG463.-
1.W
3UG463.-2.A 3UG463.-2.L 3UG463.-
2.W
Ambient
temperature
during operating
°C
-25 … +60
during storage
°C -40 … +85 85 … -40 -40 … +85
during transport
°C
-40 … +85 85 … -40 -40 … +85
Design of the
electrical isolation
Safe isolation
Galvanic isolation
between
entrance and
outlet
Yes
between the
outputs
Yes
between the
voltage supply
and other
circuits
No Yes No Yes
Mechanical
operating cycles as
operating time
typical
10 000 000
Electrical operating
cycles as operating
time at AC-15 at
230 V typical
100 000
Operating cycles
with 3RT2
contactor maximum
1/h 5 000