User Manual
3UG463. voltage monitoring relay   
11.7 Technical data 
  3UG4 / 3RR2 monitoring relays 
274  Manual, 02/2013, NEB927043002000/RS-AA/002 
    3UG463.-1.A  3UG463.-1.L  3UG463.-
1.W 
3UG463.-2.A 3UG463.-2.L  3UG463.-
2.W 
Precision  of  digital 
display 
  +/-1  digit           
Relative 
temperature-related 
measurement 
deviation 
%  0.1           
Relative  repeat 
accuracy 
%  1           
Type  of  voltage  of 
the  controlled 
supply  voltage 
  AC/DC           
Control  supply 
voltage 
•  at  50  Hz  at  AC 
–  rated  value 
V  24  17 … 275  24 … 240  24  17 … 275  24 … 240 
•  at  60  Hz  at  AC 
–  rated  value 
V  24  17 … 275  24 … 240  24  17 … 275  24 … 240 
•  for  DC 
–  rated  value 
V  24  17 … 275  24 … 240  24  17 … 275  24 … 240 
Working  range 
factor  supply 
voltage  rated  value 
•  at  50  Hz  for 
AC 
0.85 … 1.15  1  0.85 … 1.1  0.85 … 1.15  1  0.85 … 1.1 
•  at  60  Hz  for 
AC 
0.85 … 1.15  1  0.85 … 1.1  0.85 … 1.15  1  0.85 … 1.1 
•  for  DC 
0.85 … 1.15  1  0.85 … 1.1  0.85 … 1.15  1  0.85 … 1.1 
Impulse  voltage 
resistance  rated 
value 
kV  4           
Recorded  real 
power 
W  2           
Protection  class  IP   IP20           
Electromagnetic 
compatibility 
  IEC  60947-1  /  IEC  61000-6-2  /  IEC  61000-6-4 
Operating  current 
at  17  V  minimum 
mA  5           
Continuous  current 
of  the  DIAZED 
fuse link of the 
output  relay 
A  4           
Resistance  against 
vibration  according 
to  IEC  60068-2-6 
  1 … 6 Hz: 15 mm, 6 … 500 Hz: 2g 