User Manual
  System overview 
  3.4 Mounting / removal 
3UG4 / 3RR2 monitoring relays 
Manual, 02/2013, NEB927043002000/RS-AA/002 
27 
Direct mounting on 3RT2 contactor / 3RF34 (size S0) solid-state contactor 
The diagram below shows an example mounting scenario based on mounting the 
3RR21 analog setting current monitoring relay, size S0, on the 3RT2 contactor. 
Table 3- 7  Mounting of 3RR2 current monitoring relay, screw-type connection system (size S0) 
Step  Operating instruction  Figure 
1  Push the current monitoring relay into 
the contactor from below. Attach the 
two hooks on the current monitoring 
relay to the two openings on the rear 
of the contactor. This pushes the 
main current contacts into the 
corresponding terminals on the 
contactor. 
2  Tighten the screws on the contactor 
with a Pozidriv size 2 (S00) or 
Pozidriv size 3 (S0) screwdriver 
(tightening torque 0.8 to 1.2 Nm). 
Check that the cable is clamped tight. 
Note 
The connection cross-section of the removable and permanently connected terminal blocks 
with screw-type connection are described in Chapter "Screw-type connection (Page 19)." 










