3UG458. insulation monitoring relay.
10.4 3UG4582/3UG4583 insulation monitoring relays
3UG4 / 3RR2 monitoring relays
242 Manual, 02/2013, NEB927043002000/RS-AA/002
Operating state LED (green) LED F (red) LED (yellow)
L+/L- open circuit at
system start
1)
/
Test function
1)
/
Dependent on the configuration
System discharge
capacity too
high/measured result
invalid
• On the 3UG4582: Off
• On the 3UG4583: Dependent
on the configuration
Internal fault
• On the 3UG4582:
Off
• On the 3UG4583:
Dependent on the
configuration
• On the 3UG4582: Off
• On the 3UG4583: Dependent
on the configuration
Setting error
1), 2)
Test function
Off
• On the 3UG4582: Off
• On the 3UG4583: Dependent
on the configuration
Manual RESET
possible
3)
4)
1)
Only on the 3UG4583-1CW30.
2)
Possible setting error: The threshold for shutdown is set to a higher value than the warning
threshold, and non-volatile (retentive) fault storage is set simultaneously with autoreset.
3)
The device has tripped following an insulation fault. The fault has been stored and the insulation
resistance has reverted to a value above the set threshold including hysteresis.
4)
Dependent on the fault.
The switching behavior of the output relay is shown in Chapter "Functions (Page 227)".