  10.4 3UG4582/3UG4583 insulation monitoring relays 
3UG4 / 3RR2 monitoring relays 
Manual, 02/2013, NEB927043002000/RS-AA/002 
241 
Carrying out the self-test 
The test function is only possible if there is no fault. 
By operating the combined test/reset button, the insulation monitoring relay goes through an 
internal test that checks the proper functioning of the operational device. 
The output relays do not pick up or they switch to the fault status while the Test/Reset button 
is pressed, while control contact Y1-Y3 is closed, or while the test functions execute after 
application of the supply voltage. The test function can be started again at any time via the 
Test/Reset button on the front or via a remote test button. The graphic below shows the 
connection of the button for the remote test. 
<
<
<
Figure 10-9  Remote test button 
10.4.4  Diagnostics 
10.4.4.1  Diagnostics with LEDs 
Status display 
The following information indicates the operating state on the 3UG4582/3UG4583 insulation 
monitoring relays: 
Operating state  LED 
 (green)  LED F (red)  LED   (yellow) 
Start 
Off  Off 
No fault 
Off 
•  On the 3UG4582: 
•  On the 3UG4583: Dependent 
on the configuration 
Advance warning
1)
Insulation fault 
(threshold undershot) 
•  On the 3UG4582: Off 
•  On the 3UG4583: Dependent 
on the configuration 
PE/KE open circuit 
•  On the 3UG4582: Off 
•  On the 3UG4583: Dependent 
on the configuration 