10.4 3UG4582/3UG4583 insulation monitoring relays
3UG4 / 3RR2 monitoring relays
Manual, 02/2013, NEB927043002000/RS-AA/002
241
Carrying out the self-test
The test function is only possible if there is no fault.
By operating the combined test/reset button, the insulation monitoring relay goes through an
internal test that checks the proper functioning of the operational device.
The output relays do not pick up or they switch to the fault status while the Test/Reset button
is pressed, while control contact Y1-Y3 is closed, or while the test functions execute after
application of the supply voltage. The test function can be started again at any time via the
Test/Reset button on the front or via a remote test button. The graphic below shows the
connection of the button for the remote test.
<
<
<
Figure 10-9 Remote test button
10.4.4 Diagnostics
10.4.4.1 Diagnostics with LEDs
Status display
The following information indicates the operating state on the 3UG4582/3UG4583 insulation
monitoring relays:
Operating state LED
(green) LED F (red) LED (yellow)
Start
Off Off
No fault
Off
On the 3UG4582:
On the 3UG4583: Dependent
on the configuration
Advance warning
1)
Insulation fault
(threshold undershot)
On the 3UG4582: Off
On the 3UG4583: Dependent
on the configuration
PE/KE open circuit
On the 3UG4582: Off
On the 3UG4583: Dependent
on the configuration