3UG458. insulation monitoring relay.   
10.4 3UG4582/3UG4583 insulation monitoring relays 
  3UG4 / 3RR2 monitoring relays 
230  Manual, 02/2013, NEB927043002000/RS-AA/002 
Reset response and memory function 
The device features an autoreset that resets output relay K1 to its original state after an fault 
message and rectification of the fault that has occurred. As well as autoreset, the devices 
can also be set to manual RESET by means of external switching. 
The output relay (on 3UG4583: both output relays) remains dropped out if manual RESET is 
active, and it only picks up again after actuation of the combined test/reset button, or 
following activation of remote reset (terminals Y2-Y3) if the insulation resistance is greater 
than the set threshold including hysteresis. Another method of resetting the device is by 
switching the supply voltage off and on again, provided the fault is not stored in retentive 
(non-volatile) memory. 
Connection Y2-Y3  Reset options 
<
<<
1) On the front (Test/Reset button) 
2) Remote reset (remote button with NC function) 
3) A1+ / A2- (switching the supply voltage off/on) 
<
<
<
1) On the front (Test/Reset button) 
2) A1+ / A2- (switching the supply voltage off/on) 
<
<
<
1) Autoreset (factory setting) 