User Manual
3UG458. insulation monitoring relay.   
10.4 3UG4582/3UG4583 insulation monitoring relays 
  3UG4 / 3RR2 monitoring relays 
228  Manual, 02/2013, NEB927043002000/RS-AA/002 
Monitoring 
The system to be monitored is connected to the measuring signal inputs L+, L-. The 
terminals can be connected to any conductor (phase, +/- potential, or N conductor). The 
measuring signal inputs must be connected to different conductors. 
The ground potential is connected to the terminals 
 and KE. 
KE stands for control ground and is used for monitoring the fault-free ground connection of 
the insulation monitoring relay. 
The 3UG4582 insulation monitoring relays work according to the closed-circuit principle NC. 
The 3UG4583 insulation monitoring relays work in accordance with the set relay switching 
behavior (closed-circuit principle NC or open-circuit principle NO). 
After applying the rated control and supply voltage, the insulation monitoring relay goes 
through an internal test that checks the proper functioning of the operational device. The test 
encompasses an internal test of the device at hardware and firmware level (on the 
3UG4583, a settings check is also carried out) , as well as system diagnostics with 
calculation of the system discharge capacity of the first measured value of the insulation 
resistance. If there are no internal device faults or external faults on completion of this test, 
the output relays change their switching state (if closed-circuit principle is set). The time for 
this test can be up to 10 s with purely AC systems. In AC systems with DC components, as 
is the case when rectifiers are used, up to 15 s can be needed. 
Note 
If the 3UG4583 insulation monitoring relay is used for monitoring the winding insulation of a 
motor, the function test first results in a fault message if the closed-circuit principle is 
selected, since the device is not applied to the supply voltage until a measurement is 
possible on the switched-off motor. Either this fault must be hidden by downstream logic, or 
the open-circuit principle must be set. The output relays would only pick up if an insulation 
fault or internal device faults are detected. However, the fault "Missing supply voltage" can 
then no longer be detected. 
If the measured value undershoots the set threshold in the case of the 3UG4582 insulation 
monitoring relays, output relay K1 drops out. If the measured value overshoots the threshold 
including hysteresis, output relay K1 picks up. 
The principle of operation of the 3UG4583 insulation monitoring relays can be configured via 
DIP switch 4: 
In the functional principle 1 x 2 changeover contacts, both output relays K1 and K2 respond 
to threshold R1 (warning). The settings of threshold R2 have no influence on the principle of 
operation. If the measured value undershoots the set threshold, the output relays switch to 
the fault status. If the measured value overshoots the set threshold including hysteresis, the 
output relays revert to the original state. 