User Manual
System overview   
3.3 Connection methods 
  3UG4 / 3RR2 monitoring relays 
22  Manual, 02/2013, NEB927043002000/RS-AA/002 
Catalog IC10 "Industrial Controls" (www.siemens.com/industrial-controls/catalogs) offers a 
standard screwdriver (3 mm slot) that can be used as the operating tool for opening the 
spring-loaded connections. 
Spring-loaded connection for mountable 3RR2 current monitoring relays 
The table below describes the procedure for creating a spring-loaded connection: 
DANGER 
Hazardous Voltage. 
Will cause death or serious injury. 
Turn off and lock out all power supplying this device before working on this device. 
Table 3- 3  Connecting the 3RR2 current monitoring relay spring-loaded terminal 
Step  Operating instruction  Image 
1  Insert the screwdriver into the 
bottommost (A) or topmost (B) 
operating slot on the right-hand side. 
2  Press the screwdriver down (A) or up 
(B), then push it into the operating slot 
as far as it will go. 
The screwdriver blade keeps the 
spring-loaded terminal open 
automatically. 
~10°
~10°
$
%
3  Insert the conductor into the oval 
connection slot. 
4  Remove the screwdriver. The terminal 
closes and the conductor is now 
securely clamped. 










