User Manual

3UG458. insulation monitoring relay.
10.1 Application areas
3UG4 / 3RR2 monitoring relays
206 Manual, 02/2013, NEB927043002000/RS-AA/002
10.1 Application areas
Application areas
The 3UG458. insulation monitoring relays are used in the following applications, for example:
Table 10- 1 Application areas of the insulation monitoring relays
Function Application
Insulation monitor for
ungrounded systems
Emergency power supplies
Safety lighting
Industrial production plants with high availability requirements
(chemical industry, automobile manufacture, printing)
Shipbuilding and railways
Mobile power generators (aircraft)
Renewable energies (wind energy and photovoltaic plants)
Mining industry
Table 10- 2 Functions of the 3UG4581/3UG4582/3UG4583 insulation monitoring relays
Insulation monitoring relays
Function
3UG4581 3UG4582 3UG4583
Insulation monitoring
Monitoring for open circuit
1)
Monitoring for incorrect settings
Control circuit monitoring 1p 1p 1p
Main circuit monitoring 1p, 3p, 3p + N 1p, 2p, 2p + N, 3p,
3p + N
1p, 2p, 2p + N, 3p,
3p + N
✓: Function available
1p: Monitoring is 1-phase
2p: Monitoring is 2-phase
2p + N: Monitoring is 2-phase + N conductor
3p: Monitoring is 3-phase
3p + N: Monitoring is 3-phase + N conductor
— : Function not available
1)
Configurable