9.5 Diagnostics
3UG4 / 3RR2 monitoring relays
198 Manual, 02/2013, NEB927043002000/RS-AA/002
Display
area
Symbol Meaning
,
Measurement range exceeded (> 40 A)
0.00A Fallen below measurement range
Open-circuit
Short-circuit
You will find more information about the switching behavior of the output relay in Chapter
"Functions (Page 189)."
9.5.2 Reset
RESET
How the outputs are reset depends on the "Reset response" parameter (see Chapter "Reset
response (Page 351)").
The following settings can be selected:
Automatic
reset (Memory = O / Mem = no)
The device is reset automatically as soon as a previously occurring error has been dealt
with.
Manual RESET (Memory = I / Mem = yes)
To reset the devices with digital setting, it is necessary to press both arrow keys
simultaneously for more than 2.5 s after removal of the cause of error. If the cause of the
error has not been removed, a new error message appears immediately. Alternatively,
the devices can be reset by switching the rated control supply voltage on and off.
Note
The warning threshold is always reset by autoreset.