8.4  Operation 
Parameters  
Parameterization of the devices is possible locally using the display and the three keys. 
Parameter information 
The table below shows the settable parameter information of the 3UG4624 residual current 
monitoring relay: 
Table 8- 2  Parmeter information, 3UG4624 residual monitoring relays with digital setting 
Setting range 
Menu 
level 
Parameters 
Minimum value  Maximum value 
Increment  Factory 
setting 
"RUN"  Threshold for current overshoot 
(I▲) 
depending on IΔn
 1)
  depending on IΔn
 1)
  depending on 
IΔn
 1)
depending 
on IΔn
 1)
"RUN"  Warning threshold for current 
overshoot (I!) 
depending on IΔn
 1)
  depending on IΔn
 1)
  depending on 
IΔn
 1)
depending 
on IΔn
 1)
"SET"  Rated residual current of the 
summation current transformer 
(IΔn) 
0,3 A  40.0 A  0.1 A  10.0 A 
"SET"  Hysteresis (Hyst)  depending on IΔn
 1)
  depending on IΔn
 1)
  depending on 
IΔn
 1)
depending 
on IΔn
 1)
"SET"  ON-delay time (onDel)  0.1 s  20.0 s  0.1 s  0.1 s 
"SET"  Tripping delay time (I▲Del)  0.1 s  20.0 s  0.1 s  0.1 s 
"SET"  Reset response (Mem)  no = Autoreset  yes = Hand-RESET  --  no = Auto-
reset 
"SET"  Relay switching behavior 
(closed-circuit principle NC / 
open-circuit principle NO) 
NC or NO  --  NC 
1) 
  The value depends on the parameter "Rated residual current of the summation current transformer (IΔn)." You can take 
the value from the table "Parameter information depending on the rated residual current" in the next section. 