User Manual
3UG4624 residual current monitoring relay   
8.3 Functions 
  3UG4 / 3RR2 monitoring relays 
174  Manual, 02/2013, NEB927043002000/RS-AA/002 
Monitoring 
If the measured residual current exceeds the set warning threshold (I!), the associated CO 
contact 21-22-24 changes the switching state without delay and a (!) appears on the display 
as an indication. If the measured fault current exceeds the set threshold (I▲), the set delay 
time (I▲Del) starts and the associated relay symbol flashes. After this time has expired, the 
associated CO contact 11-12-14 changes the switching state. 
On the display, the currently displayed measuring value and the symbol for overshoot flash. 
Note 
The neutral conductor must no longer be grounded after the summation current transformer 
because otherwise the residual current monitoring function cannot be ensured. 
Startup delay 
To be able to start a drive, the output relay switches to the correct state during the ON-delay 
time (onDel) depending on the selected open-circuit principle or closed-circuit principle, even 
if the measured value is still under the set value. 
Tripping delay 
If the measured value overshoots or undershoots the set threshold after expiry of the ON-
delay time (onDel), the set tripping delay time (Del) and the relay symbol will flash. After 
expiry of this time, the output relays change the switching state. On the display, the current 
measuring value and the symbol for undershoot or overshoot flash. 
Note 
The 3UG4624 residual current monitoring relays are only suitable for line frequencies of 50 / 
60 Hz! 
You will find the switching states of the output relays below in section "Function diagrams" 
and in Chapter "Diagnostics (Page 179)." 
Tripping conditions 
The combination of the 3UG4624 residual current monitoring relay with the 3UL22 
summation current transformer responds according to the following tripping conditions: 
Fault current monitoring relays  Fault current 
No tripping  0 to 50 % of the set threshold 
Tripping not defined  50 to 100 % of the set threshold 
Tripping  >= 100 % of the set threshold 