7.7 Technical data
3UG4 / 3RR2 monitoring relays
Manual, 02/2013, NEB927043002000/RS-AA/002
167
3UG4621-..A.. 3UG4622-..A.. 3UG4621-..W.. 3UG4622-..W..
Supply voltage 1
at 50 Hz for AC
rated value
V 24
initial rated value
V 24
final rated value
V 240
at 60 Hz for AC
rated value
V 24
initial rated value
V 240 24
final rated value
V 24 240
for DC
rated value
V 24
initial rated value
V 24
final rated value
V 240
Impulse voltage resistance
rated value
kV 4
Recorded real power W 2
Protection class IP IP20
Electromagnetic compatibility IEC 60947-1 / IEC 61000-6-2 / IEC 61000-6-4
Operating current at 17 V
minimum
mA 5
Continuous current of the
DIAZED fuse link of the
output relay
A 4
Resistance against vibration
according to IEC 60068-2-6
1 6 Hz: 15 mm, 6 500 Hz: 2g
Resistance against shock
according to IEC 60068-2-27
sinusoidal half-wave 15g / 11 ms
Current carrying capacity
of output relay
at AC-15
at 250 V at 50/60 Hz
A
3
at 400 V at 50/60 Hz
A
3
at DC-13
at 24 V
A
1
at 125 V
A
0.2
at 250 V
A
0.1
for permanent overcurrent
maximum permissible
A
0.6 15 0.6 15
for overcurrent duration <
1 s maximum permissible
A
5 50 5 50