User Manual
3UG4.1 line monitoring relay   
6.7 3UG4617 / 3UG4618 line monitoring relays 
  3UG4 / 3RR2 monitoring relays 
152  Manual, 02/2013, NEB927043002000/RS-AA/002 
    3UG4617-1....  3UG4618-1....  3UG4617-2....  3UG4618-2.... 
Distance,  to  be  maintained, 
conductive  elements 
•  forwards 
mm 
0       
•  backwards 
mm  0       
•  sidewards 
mm  0       
•  upwards 
mm  0       
•  downwards 
mm  0       
Type  of  mounting  
snap-on  mounting 
Product  function  removable 
terminal  for  auxiliary  and 
control  circuit 
  Yes       
Design  of  the  electrical 
connection 
  screw-type  terminals  spring-loaded  terminals 
Type  of  the  connectable 
conductor  cross-section 
•  solid 
1x  (0.5  ...  4  mm
2
),   
2x  (0.5  ...  2.5  mm
2
) 
2x  (0.25  ...  1.5  mm
2
) 
•  finely  stranded 
–  with  wire  end 
processing 
  1x  (0.5  ...  2.5  mm
2
),   
2x  (0.5  ...  1.5  mm
2
) 
2  x  (0.25  ...  1.5  mm
2
) 
–  without  wire  end 
processing 
  —    2x  (0.25  ...  1.5  mm
2
) 
•  for  AWG  conductors 
–  solid 
  2x  (20  ...  14)    2x  (24  ...  16)   
–  stranded 
  2x  (20  ...  14)    2x  (24  ...  16)   
Tightening  torque         
•  with  screw-type  terminals 
N·m 
0.8 … 1.2    — …   
Number  of  change-over 
switches  delayed  switching 
  2       