6.7 3UG4617 / 3UG4618 line monitoring relays
3UG4 / 3RR2 monitoring relays
Manual, 02/2013, NEB927043002000/RS-AA/002
147
Display
area
Symbol Meaning
Error
Not flashing: Relay contact 11/12 open, relay contact 11/14 closed
Flashing: Delay time (tripping delay) is running
Masked out: Relay contact 11/12 closed, relay contact 11/14 open
Not flashing: Relay contact 21/22 open, relay contact 21/24 closed
Masked out: Relay contact 21/22 closed, relay contact 21/24 open
Note
CO contact 1 switches on all types of error.
CO contact 2 is for operating a reversing combination.
You will find more information about the switching behavior of the output relays in Chapter
"Functions (Page 142)."
6.7.4.2 Reset
RESET
How the outputs are reset depends on the "Reset response" parameter (see Chapter "Reset
response (Page 351)").
The following settings can be selected:
Automatic
reset (Memory = O / Mem = no)
The device is reset automatically as soon as a previously occurring error has been dealt
with.
Manual RESET (Memory = I / Mem = yes)
To reset the devices with digital setting, it is necessary to press both arrow keys
simultaneously for more than 2.5 s after removal of the cause of error. If the cause of the
error has not been removed, a new error message appears immediately. Alternatively,
the devices can be reset by switching the rated control supply voltage on and off.