User Manual
  3UG4.1 line monitoring relay 
  6.7 3UG4617 / 3UG4618 line monitoring relays 
3UG4 / 3RR2 monitoring relays 
Manual, 02/2013, NEB927043002000/RS-AA/002 
147 
Display 
area 
Symbol  Meaning 
③ 
Error 
•  Not flashing: Relay contact 11/12 open, relay contact 11/14 closed 
•  Flashing: Delay time (tripping delay) is running 
•  Masked out: Relay contact 11/12 closed, relay contact 11/14 open 
③ 
•  Not flashing: Relay contact 21/22 open, relay contact 21/24 closed 
•  Masked out: Relay contact 21/22 closed, relay contact 21/24 open 
Note 
CO contact 1 switches on all types of error. 
CO contact 2 is for operating a reversing combination. 
You will find more information about the switching behavior of the output relays in Chapter 
"Functions (Page 142)." 
6.7.4.2  Reset 
RESET 
How the outputs are reset depends on the "Reset response" parameter (see Chapter "Reset 
response (Page 351)"). 
The following settings can be selected: 
●  Automatic
 reset (Memory = O / Mem = no) 
The device is reset automatically as soon as a previously occurring error has been dealt 
with. 
●  Manual RESET (Memory = I / Mem = yes) 
To reset the devices with digital setting, it is necessary to press both arrow keys 
simultaneously for more than 2.5 s after removal of the cause of error. If the cause of the 
error has not been removed, a new error message appears immediately. Alternatively, 
the devices can be reset by switching the rated control supply voltage on and off. 