User Manual

3UG4.1 line monitoring relay
6.6 3UG4615 / 3UG4616 line monitoring relays
3UG4 / 3RR2 monitoring relays
Manual, 02/2013, NEB927043002000/RS-AA/002
137
6.6.6 Technical data
Measuring circuit
3UG4615-..... 3UG4616-.....
Type of voltage for monitoring AC
Number of poles for main current circuit 3
Measurable voltage
for AC
V
160 … 690
Adjustable voltage range V
160 … 690
Adjustable response delay time with lower or
upper limit violation
s 0.1 … 20
General technical details
3UG4615-..... 3UG4616-.....
Product function Phase monitoring relay
Design of the display LCD
Type of display LED No
Product function
undervoltage recognition
Yes
overvoltage recognition
Yes
phase sequence recognition
Yes
phase disturbance recognition
Yes
asymmetry recognition
Yes
overvoltage recognition of 3 phases
Yes
undervoltage recognition of 3 phases
Yes
tension window recognition of 3 phases
Yes
reset external
self-reset
Yes
open-circuit or closed-circuit current principle
Yes
Starting time after the control supply voltage has
been applied
s
1
Response time maximum s 0.45
Relative adjustment accuracy % 0.2
Relative metering precision % 5
Precision of digital display +/-1 digit
Relative repeat accuracy % 1