User Manual
3UG4.1 line monitoring relay   
6.3 3UG4512 line monitoring relay 
  3UG4 / 3RR2 monitoring relays 
104  Manual, 02/2013, NEB927043002000/RS-AA/002 
    3UG4512-..... 
Type  of  voltage  of  the  controlled  supply  voltage  AC 
Control  supply  voltage   
•  at  50  Hz  at  AC  rated  value 
V 
160 … 690 
•  at  60  Hz  at  AC  rated  value 
V  160 … 690 
Working  range  factor  supply  voltage  rated  value  
•  at  50  Hz  for  AC 
1 
•  at  60  Hz  for  AC 
  1 
Impulse  voltage  resistance  rated  value kV 
6 
Recorded  real  power W 2 
Protection  class  IP  IP20 
Electromagnetic  compatibility  IEC  60947-1  /  IEC  61000-6-2  /  IEC 
61000-6-4 
Operating  current  at  17  V  minimum mA 5 
Continuous  current  of  the  DIAZED  fuse  link  of  the  output  relay A 4 
Resistance  against  vibration  according  to  IEC  60068-2-6  1 … 6 Hz: 15 mm, 6 … 500 Hz: 2g
Resistance  against  shock  according  to  IEC  60068-2-27  sinusoidal  half-wave  15g  /  11  ms 
Current  carrying  capacity  of  output  relay   
•  at  AC-15 
–  at  250  V  at  50/60  Hz 
A  3 
–  at  400  V  at  50/60  Hz 
A 
3 
•  at  DC-13 
–  at  24  V 
A  1 
–  at  125  V 
A 
0.2 
–  at  250  V 
A 
0.1 
Installation  altitude  at  a  height  over  sea  level  maximum m 2 000 
Conductor-bound  parasitic  coupling  BURST  according  to  IEC  61000-
4-4 
  2  kV 
Conductor-bound  parasitic  coupling  conductor-earth  SURGE 
according  to  IEC  61000-4-5 
  2  kV 
Conductor-bound  parasitic  coupling  conductor-conductor  SURGE 
according  to  IEC  61000-4-5 
  1  kV 
Electrostatic  discharge  according  to  IEC  61000-4-2  6  kV  contact  discharge  /  8  kV  air 
discharge 
Field-bound  parasitic  coupling  according  to  IEC  61000-4-3  10  V/m 
Thermal  current  of  the  contact-affected  switching  element  maximum A  5 
Insulation  voltage  for  overvoltage  category  III  according  to  IEC 
60664  with  degree  of  pollution  3  rated  value 
V  690 
Degree  of  pollution  3 