Datasheet

• for auxiliary and control current circuit screw-type terminals
• for main current circuit screw-type terminals
Product function
• removable terminal for auxiliary and control circuit Yes
• removable terminal for main circuit Yes
Type of the connectable conductor cross-sections
• solid 1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
• finely stranded
• with wire end processing 1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
• for AWG conductors
• solid 2x (20 ... 14)
• stranded 2x (20 ... 14)
Tightening torque
• with screw-type terminals N·m 0.8 … 1.2
Outputs:
Number of NO contacts / delayed switching 0
Number of NC contacts / delayed switching 0
Number of change-over switches / delayed switching 1
Current carrying capacity
• of output relay
• at AC-15
• at 250 V / at 50/60 Hz A 3
• at 400 V / at 50/60 Hz A 3
• at DC-13
• at 24 V A 1
• at 125 V A 0.2
• at 250 V A 0.1
• for permanent overcurrent / maximum permissible A 0.6
• for overcurrent duration < 1 s / maximum permissible A 5
Operating current / at 17 V / minimum A 0.0050
Continuous current / of the DIAZED fuse link of the output relay A 4
Thermal current / of the contact-affected switching element /
maximum
A 5
Mechanical operating cycles as operating time / typical 10,000,000
Electrical operating cycles as operating time / at AC-15 / at 230
V / typical
100,000
Operating cycles / with 3RT2 contactor / maximum 1/h 5,000
Certificates/approvals:
3UG4621-1AW30
Page 4/ 06/04/2014
subject to modifications
© Copyright Siemens AG 2014
6