Datasheet
Relative temperature-related measurement deviation % 5
Temperature drift per °C %/°C 0.1
Relative repeat accuracy % 1
General technical details:
Design of the display LCD
Product function
• overcurrent recognition of 1 phase Yes
• overcurrent recognition of 3 phases No
• undercurrent recognition of 1 phase Yes
• undercurrent recognition of 3 phases No
• overcurrent recognition DC Yes
• undercurrent recognition DC Yes
• current window recognition DC Yes
• reset external Yes
• self-reset Yes
• open-circuit or closed-circuit current principle Yes
Starting time / after the control supply voltage has been applied ms 1,000
Type of / supply voltage AC/DC
Supply voltage / 1
• at 50 Hz
• for AC V 24 … 240
• at 60 Hz
• for AC V 240 … 24
• for DC V 24 … 240
Impulse voltage resistance / rated value kV 4
Recorded real power W 2
Protection class IP IP20
Electromagnetic compatibility IEC 60947-1 / IEC 61000-6-2 / IEC 61000-6-4
Resistance against vibration / according to IEC 60068-2-6 1 ... 6 Hz: 15 mm, 6 ... 500 Hz: 2g
Resistance against shock / according to IEC 60068-2-27 sinusoidal half-wave 15g / 11 ms
Installation altitude / at a height over sea level / maximum m 2,000
Conductor-bound parasitic coupling BURST / according to IEC
61000-4-4
2 kV
Conductor-bound parasitic coupling conductor-earth SURGE /
according to IEC 61000-4-5
2 kV
Conductor-bound parasitic coupling conductor-conductor
SURGE / according to IEC 61000-4-5
1 kV
Electrostatic discharge / according to IEC 61000-4-2 6 kV contact discharge / 8 kV air discharge
Field-bound parasitic coupling / according to IEC 61000-4-3 10 V/m
3UG4621-1AW30
Page 2/ 06/04/2014
subject to modifications
© Copyright Siemens AG 2014
6