3UG Monitoring Relays for Electrical and Additional Measurements
Current monitoring
72
Siemens ยท 2010
Wiring diagram for 24 V AC/DC (only 3UG46 2.-.AA30)
From the following circuit diagrams it is clear that loads in mea-
suring circuits have to be in the current flow upstream from the
monitoring relay. Otherwise, the monitoring relay could be de-
stroyed and the short-circuit current could cause damage to the
plant.
Configuring note:
A2 and M are electrically connected internally!
For applications in which the load to be monitored and the mon-
itoring relay are supplied from the same power supply, there is
no need for connection A2!
The load current must always flow through M or the monitoring
relay may be destroyed!
< >