Data Sheet
● at 24 V
10A
● at 230 V
10A
● maximum
10A
Operating current
● of auxiliary contacts
— at AC-14
— at 125 V
10A
— at AC-15
— at 24 V
10A
— at 230 V
5.6A
— at 400 V
3.6A
Operating current
● of auxiliary contacts at DC-12
— at 24 V
10A
— at 110 V
8A
— at 220 V
2A
Operating current
● of auxiliary contacts at DC-13
— at 24 V
10A
— at 60 V
5A
— at 110 V
2.4A
— at 220 V
1.1A
Installation/ mounting/ dimensions
Mounting type snap-on mounting
Width 14mm
Height 81mm
Depth 72.5mm
Connections/Terminals
Type of electrical connection for auxiliary and control
current circuit
screw-type terminals
Type of connectable conductor cross-sections
● for auxiliary contacts
— finely stranded
— with core end processing
2x (0.5 ... 1.0 mm²), 2x (0.75 ... 2.5 mm²)
● at AWG conductors for auxiliary contacts
2x (18 ... 12)
Safety related data
Product function positively driven operation acc. to
IEC 60947-5-1
Yes
Certificates/approvals
3TY6561-1A Subject to change without notice
Page 2/
5
09/13/2019 © Copyright Siemens