Datasheet
Power Relays/Miniature Contactors
3TG10 contactors
4-pole, 4 kW
3/233
Siemens IC 10 · 2011
3
Type 3TG10
AC capacity
Switching gas discharge lamps with correction, ECG
Per main current path 230 V, 50 Hz
Rated power per lamp/capacitance/
rated operational current per lamp
• Shunt compensation L18 W 4.5 µF 0.11 A Unit(s) 15
L36 W 4.5 µF 0.21 A Unit(s)
15
L58 W 7 µF 0.32 A Unit(s)
10
• With ECG (single lamp) L18 W 6.8 µF 0.10 A Unit(s)
39
L36 W 6.8 µF 0.18 A Unit(s)
39
L58 W 10 µF 0.27 A Unit(s)
26
• With ECG (two lamps) L18 W 10 µF 0.18 A Unit(s)
2 x 26
L36 W 10 µF 0.35 A Unit(s)
2 x 26
L58 W 22 µF 0.52 A Unit(s)
2 x 12
Utilization category AC-5b, switching incandescent lamps
Per main current path at 230 V, 50 Hz
kW
1.6
Load rating with DC
Utilization category DC-1, switching resistive load (L/R ≤ 15 ms)
• Rated operational currents I
e
- 1 conducting path Up to 24 V A 16
60 V A
6
110 V A
2
220 V/240 V A
0.8
- 2 conducting paths in series Up to 24 V A
16
60 V A
16
110 V A
6
220 V/240 V A
1.6
- 3 conducting paths in series Up to 24 V A
18
60 V A
18
110 V A
16
220 V/240 V A
6
- 4 conducting paths in series Up to 24 V A
20
60 V A
20
110 V A
20
220 V/240 V A
20
Utilization category DC-3 and DC-5
Shunt-wound and series-wound motors (L/R ≤ 15 ms)
• Rated operational currents I
e
- 1 conducting path Up to 24 V A 10
60 V A
0.5
110 V A
0.15
220 V/240 V A
0
- 2 conducting paths in series Up to 24 V A
16
60 V A
5
110 V A
0.35
220 V/240 V A
0
- 3 conducting paths in series Up to 24 V A
16
60 V A
16
110 V A
10
220 V/240 V A
1.75
- 4 conducting paths in series Up to 24 V A
18
60 V A
16
110 V A
10
220 V/240 V A
2
Conductor cross-sections
Screw terminals
Terminal screws
M3
• Finely stranded with end sleeve (DIN 46228 Form A/D/C) mm
2
2 x (0.75 ... 2.5)
• Solid mm
2
2 x (1 ... 2.5), 1 x 4
Permissible opening tool (screwdriver)
3.0 mm x 0.5 mm (3RA29 08-1A) or Pozidriv 2
Flat connectors
• Finely stranded 6.3 mm plug-in sleeve acc. to DIN 46245/46247
- 6.3 ... 1 mm
2
0.5 ... 1
- 6.3 ... 2.5 mm
2
1 ... 2.5
s
and
u
rating (screw terminals)
Rated insulation voltage AC V 600
Uninterrupted current Open and enclosed A
20
Maximum horsepower ratings
(
s
and
u
approved values), rated power for induction motors with 60 Hz
Single-phase/Three-phase
At 115 V hp
0.5/ --
200 V hp
1/ 3
230 V hp
1.5/ 3
460 ... 600 V hp
0/ 5
IC10_03.book Seite 233 Mittwoch, 15. Dezember 2010 2:20 14
© Siemens AG 2010