Overview
Version
The 3TG10 power relays/miniature contactors with 4 main con-
tacts are available with screw terminals or 6.3 mm × 0.8 mm flat
connectors. The versions with screw terminals are climate-proof
and finger-safe according to EN 61140.
The 3TG10 miniature contactors are characterized by their width
of only 36 mm.
Surge suppression
The 3TG10 power relays/miniature contactors have an inte-
grated protective circuit against opening surges.
■
Application
Because they are hum-free they are suitable for use in house-
hold appliances and distribution boards in office and residential
areas. They can also be used for applications where there is little
space such as air conditioners, heating systems, pumps and
fans, i. e. for simple electrical controls.
AC and DC operation
EN 60947-1, EN 60947-4-1, EN 60947-5-1
Overload and short-circuit protection
The 3UA7 overload relay can be used for overload protection.
This applies to mounting onto contactors and to stand-alone
installation.
■
Technical specifications
1)
If the three main current paths carry a load of 20 A, the following applies if
I > 10 A in the fourth conducting path: Permissible ambient temperature
40 °C.
Type 3TG10
Dimensions (W x H x D) mm
36 x 56 x 56
• With 3UA7 overload relay mounted below mm
45 x 100 x 62
General data
Endurance
• Mechanical Operating cycles 3 million
• Electrical
-AC-1 at I
e
Operating cycles 0.1 million
-AC-3 at I
e
Operating cycles 0.4 million
Rated insulation voltage U
i
(pollution degree 3) V 400
Rated impulse withstand voltage U
imp
kV 4
Protective separation
Between the coil and the contacts acc. to EN 60947-1, Appendix N V AC
Up to 300
Permissible ambient temperature
• During operation
1)
°C -25 ... + 55
• During storage °C
-50 ... + 80
Degree of protection acc. to IEC 60947-1 and EN 60529
IP00, drive system IP20
Control circuit
Power consumption of the solenoid coils (when coil is cold and 1.0 x U
s
)
• AC operation, 45 ... 450 Hz VA 4.4
-P.f.
0.9 (hum-free)
• DC operation W
4
Coil operating range
0.85 ... 1.1 x U
s
Short-circuit protection
Fuse links operational class gG
Type LV HRC 3NA, DIAZED 5SB, NEOZED 5SE
acc. to EN 60947-4-1
• Type of coordination "1" A 25
• Type of coordination "2" A
10
Miniature circuit breakers, C characteristic A
10
AC capacity
Utilization category AC-1, switching resistive loads
Rated operational current I
e
up to 400 V at 55 °C
1)
A 20 for screw terminals, 16 for flat connector
Rated power U
e
for AC loads with p.f. = 1, 230/220 V
• For screw terminals kW 7.5 (13 at 400 V)
• For flat connector kW
6 (10 at 400 V)
Minimum conductor cross-section for load with I
e
mm
2
2.5
Utilization categories AC-2 and AC-3
Operational current for AC-3 at 400 V rated value A8.4
Rated power for slipring or squirrel-cage motors
with 50 and 60 Hz and at 400 V
kW
4
Utilization category AC-5a (permissible nominal impedance: ≥ 0.5 Ω)
Switching of gas discharge lamps
Per main current path at 230 V, 50 Hz
Rated power/rated operational current per lamp
• Uncorrected 18 W 0.37 A 43
36 W 0.43 A
37
58 W 0.67 A
24
• DUO switching 18 W 2 x 0.11 A
2 x 81
36 W 2 x 0.21 A
2 x 42
58 W 2 x 0.32 A
2 x 28
W
H
D
IC10_03.book Seite 232 Mittwoch, 15. Dezember 2010 2:20 14