Datasheet
● of the enclosure
IP40
● of the terminal
IP20
Shock resistance
● acc. to IEC 60068-2-27
Sinusoidal half-wave 50 g / 11 ms
● for railway applications acc. to DIN EN 61373
Category 1, Class B
Operating period typical 100000h
Reference code acc. to DIN EN 81346-2 P
Reference code acc. to DIN EN 61346-2 P
Operating voltage
● at AC
— at 50 Hz rated value
6...24V
— at 60 Hz rated value
6...24V
● at DC
— rated value
6...24V
Relative positive tolerance of the operating voltage 20%
Relative negative tolerance of the operating voltage 20%
Control circuit/ Control
Inrush current maximum 2A
Connections/Terminals
Type of electrical connection screw-type terminals
Type of connectable conductor cross-sections
● solid with core end processing
2x (0.5 ... 0.75 mm²)
● solid without core end processing
2x (1.0 ... 1.5 mm²)
● finely stranded with core end processing
2x (0.5 ... 1.5 mm²)
● finely stranded without core end processing
2x (1,0 ... 1,5 mm²)
● at AWG conductors
2x (18 ... 14)
Tightening torque
● with screw-type terminals
0.8...0.9N·m
Lamp
Type of light source LED
Color of the light source white
Light intensity 900...1400mcd
Certificate of suitability
● ATEX
No
● IECEx
No
Ambient conditions
Ambient temperature
● during operation
-25...+70°C
● during storage
-40...+80°C
Environmental category during operation acc. to IEC
60721
3M6, 3S2, 3B2, 3K6 (with relative air humidity of 10 ... 95 %, no
condensation in operation permitted)
3SU1401-1BG60-1AA0 Subject to change without notice
Page 2/
5
02/22/2019 © Copyright Siemens