  10.1 Configuring the IO-Link 
SIRIUS ACT 3SU1 pushbuttons and signaling devices 
System Manual, 02/2015, A5E03457306020A/RS-AB/002 
209 
10.1.3.3
Configuration 
Configuring the IO-Link device with the S7-PCT port configuration tool 
1.  Start the 
S7-PCT
 port configuration tool. 
2.  Create a new project or open an existing project as described in the online help. 
3.  Select a bus category (PROFIBUS DP/PROFINET IO). 
4.  Select an IO-Link master. 
5.  Select the IO-Link device in the component catalog of the 
S7-PCT
 port configuration tool. 
6.  Drag the IO-Link device out of the component catalog to the required port of the IO-Link 
master. 
7.  Load the configuration into the IO-Link master before parameterizing the IO-Link device. 
8.  Start by parameterizing the IO-Link device. 
Additional information is available in the 
S7-PCT
 online help. 
Note 
To be able to access the IO-Link master or an IO-Link device online, communication 
between the ET 200 and the higher-level controller must be active (BF LED on ET 200 
interface module is off). 
10.1.4
Acyclic data exchange with the IOL_CALL function block 
For acyclic data exchange, the "IOL_Call" function block is available as a download for 
controllers of the S7 families.  
The block supports you in the following tasks:  
●  Parameterization of an IO-Link device during operation 
●  Executing IO-Link port functions 
●  Backing up/restoring IO-Link device parameters 
●  Backing up/restoring IO-Link master parameters 
Requirements 
●  Install the "IOL_Call" function block. 
You can download the IOL_Call function block and the description from the Internet 
(https://support.industry.siemens.com/cs/ww/en/view/82981502). 