User Manual
  IO-Link 
  10.1 Configuring the IO-Link 
SIRIUS ACT 3SU1 pushbuttons and signaling devices 
System Manual, 02/2015, A5E03457306020A/RS-AB/002 
207 
You will find further information on the IOL_Call function block in Section "Acyclic data 
exchange with the IOL_CALL function block (Page 209)". 
10.1.2.2
Configuration 
Configuring the IO-Link master in 
HW Config
1.  Start the SIMATIC Manager (
STEP 7 
) or the TIA Portal and configure the project as 
described in the 
STEP 7
 online help. 
2.  Select the IO-Link master in the hardware catalog of 
HW Config
. 
3.  Drag and drop the IO-Link master from the hardware catalog to the configuration table. 
4.  Select the IO-Link master in the configuration table (
STEP 7 
)/ device view (TIA Portal). 
5.  Press the right mouse button and select "
Object Properties
" from the shortcut menu. 
Result
: The "
Properties
" window of the IO-Link master opens. 
6.  Check the settings of the addresses. 
Every IO-Link master port needs a corresponding overall address range depending on 
the IO-Link device used. 
Configuring the IO-Link device with the S7-PCT port configuration tool 
1.  Select the configured IO-Link master. 
2.  Press the right mouse button and select "
Start device tool
" (
STEP 7
 or 
TIA Portal)/"
Configure IO-Link
" (
STEP 7
 or TIA Portal) from the shortcut menu depending 
on the configuration tool used. 
3.  Select the IO-Link device in the component catalog of the S7-PCT port configuration tool. 
4.  Drag the IO-Link device out of the component catalog to the required port of the IO-Link 
master. 
5.  Start by parameterizing the IO-Link device. 
Additional information is available in the 
S7-PCT
 online help. 










